TRIPP LITE SU6000RT3U 6000 VA 4200 Watts Hardwire Outlets Smart Online Expandable Rack / Tower UPS System
VPN: SU6000RT3U
Vendor: Tripp Lite
Price: $0.00 - $0.00 CAD from 0 stores » Email this product to a friend » Write a review
» Discuss on forum » Post your deal
Vendor: Tripp Lite
Price: $0.00 - $0.00 CAD from 0 stores » Email this product to a friend » Write a review
» Discuss on forum » Post your deal
Product Specifications
Model | |
Brand | TRIPP LITE |
Model | SU6000RT3U |
Input | |
Input Voltage Range | 208V AC |
Input Frequency | 50/60 Hz |
Output | |
VA Rating | 6000 VA |
Watts | 4200 Watts |
Output Voltage | 208V & 120V AC |
Outlets | Hardwire |
Battery | |
Battery Run Time | Full load runtime: Included batteries — 15 min (6000VA) add 1 BP240V10RT3U — 37 min. Half load runtime: Included batteries — 37 min. (3000VA) Add 1 BP240V10RT3U — 79 min. |
Battery Recharge Time | 2-4 hours to 90% |
Spec | |
Interface Port | RS-232 |
Management Software | YES |
Approvals | UL1778 (USA), cUL (Canada), CE (Europe), Class A (emissions), NOM (Mexico),GOST, IRAM, SASO |
Physical Spec | |
Rackmountable | Rack/Tower (9U) |
Weight | Power Module: 41.8 lbs.Battery Pack: 136.5 lbs.Step-down Transformer: 90 lbs. |
Dimensions | Power Module 5.14 x 17.5 x 22.5, Battery Pack 5.14 x 17.5 x 23.5, Step-down Transformer 5.14 x 17.5 x 26 (Step-down transformer max depth is 24 inches when compatible SUPDM backplate is used) |
Features | |
Features | True on-line, double conversion UPS provides pure, sine wave AC output at all times Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems 6000VA / 4200 watt power capacity with hardwire input / output connections Accepts input voltages between 156 and 276, regulating output within 2% of selectable 208 and 120V AC output Standard included 3U battery pack provides 37 minutes runtime at half load (3000VA) and 15 minutes at full load (6000VA) Expandable runtime with multiple external battery packs (part# BP240V10RT3U or BP240V32) Innovative design makes unit adaptable for rackmount, tower, or stacking applications Power module and battery pack require only 3 rack spaces each (9U total rack space usage) DB9 serial port for network interface; SNMP compatible Slot for optional SNMP/web card SNMP/Web card for accessory slot (SNMPWEBCARD) PowerAlert unattended shutdown software and 6 ft. network cable included Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or suffers an internal failure that requires service Manual bypass switch on the transformer module allows users to disconnect, remove, and replace the power module while maintaining continuous utility power to connected equipment Diagnostic LEDs Mounting hardware included with each 3U module for 4 post rackmount installation, 2 post telecom rack compatible with separate purchase 2POSTRMKITWM accessory (3 required) |